Instrumentation

PRODUCT DATASHEET
Air Flow Gauges  DPT-Flow
Acronym
Title
Cod
Brand

DPT-Flow

Air Flow Gauges


Marchio Qflow
expand
DESCRIPTION
Strumentazione - Air Flow Gauges  DPT-Flow

DPT-Flow

Air Flow Gauges

Each device is individually temperature compensated. Each device has autozero element which makes it fully maintenance free.
Supported FAN manufacturers: Fläkt Woods, Rosenberg, Nicotra, Comefri, Ziehl, Ebm-Papst, Gebhardt

DPT-Flow Tabella
**) including: general accuracy, temperature drift, linearity, hysteresis and repetition error
expand
FEATURES



Max. pressure
Bursting. pressure
Suitable media
Measuring element



MENU selections and initialisation instructions for installation



Supply voltage
Power consumption
Output signal


DPT-F1



Housing
Cover
Pressure connections
Duct connections
Tubing


Electrical connections
Cable entry
Pressure connections


Operation
Storage
Ambient Umidity


Protection standard






DPT-F4
Alphanumeric display with MENU user interface .
The display can be ordered separately for installation purposes.

25 kPa
50 kPa
Air and non-aggressive gases
Piezoresistive


MENU selections and initialisation instructions for installation
If buttons are not pressed within 20 seconds the device returns to the normal measuring mode.
1. Press Select > 2seconds to start the menu.


2. Selection of the manufacturer of FAN




3. Each FAN has its own specific K-value.
Please see the right K-value from the datasheet of the FAN:
Fläkt Woods (k=0,3…99), Rosenberg (k=37…800), Nicotra (c=10…1500), Comefri (k=23…158), Ziehl (k=10…1500), Ebm-Papst (k=10…1500)

4. The unit shown on the display m³/s, m³/h or Pa




5. Output unit for defining the output scale



6. Output scale, selectable range depends on the chosen output unit.
m³/s 10V = 5…50 m³/s
m³/h 10V = 20 000 … 200 000 m³/h
0 V is always 0 m³/s and 0 m³/h

7. Stepless response time selection.
Tr can be selected to be 1 s … 20 s.
Tr is the time when output has changed 63 % from the final value of the output.

8. Press send and the device returns the normal measuring mode


Electrical interface
24 VAC or VDC 10%
< 1.0 W
Vout 0…10 VDC, Load R minimum 1k
Pout 0…10 VDC, Load R minimum 1k
DPT-F2 DPT-F3
V out scale can be changed

Materials
ABS
ABS
ABS
ABS
PVC, soft

Connections
4 screw terminals, max 1.5 mm2
M16
Male ø 5,0 mm and 6,3 mm

General Ambient Condition
-5 ÷ + 50 °C
-20 ÷ + 70 °C
0 ÷ 95 % RH

Safety
IP54

Conformance
Meets the requirements for CE marking:
EMC directive 89/336/EEC
Rohs Directive 2002/95/EY

Auto zero element
Auto zero element makes the DPT FLOW meter maintenance free. Element automatically adjusts the transmitters zero point from time to time, this eliminates the zero point long term drift of the piezoresistive sensing element.
During zero point adjustment the output and display values will freeze to the latest measured value. The automatic zero point adjustment takes 4 seconds. Zero point adjustment is carried out every 10 minutes normally and during warm up the time is shorter a few times.
expand
DIMENSIONS

DPT2000.dwg
DPT2000.dxf
DPT2000.pdf











H_Altezza [mm]
W_Larghezza [mm]
D_Profondità [mm]
P_Peso [kg]
P_Peso con Accessori [kg]
Disegno Ingombro DPT-2fili
H_71,5 • HT_95,0
W_90
D_36
P_0,150
P_0,290